Trane X13511537-01 Thermostat Operation Manual

The Trane X13511537-01 (BAYSTAT150A) is a programmable 3H/2C push-button thermostat for commercial conventional and heat pump systems. It features an LCD display with symbols for temperature, setpoints, and modes, supporting Heat, Cool, Auto, Off, and Emergency Heat system modes, and On/Auto fan modes. It includes configurable scheduling (1/5+1+1/5+2/7-day), timed overrides (TOV), cycling rates, deadband, compressor protection, remote sensor compatibility, and error codes. Below are the key specifications and operation instructions.

1. Key Specifications 2. Operation Instructions 2.1. Initial Setup 2.2. Home Screen Navigation 2.3. Operating Modes 2.4. Settings Screen 2.5. Advanced Features 2.6. Troubleshooting 3. Installation Instructions 3.1. Pre-Installation 3.2. Wiring Diagrams 3.3. Configuration Options 4. Calculation Tool

Key Specifications

Operation Instructions

Initial Setup

1. Power On: Apply 24 VAC; performs power-up sequence (full screen, firmware, tests).
2. Set Time: From operating screen, press sequence to enter time mode; adjust hours/minutes with Up/Down; save.
3. Set System Mode: Press Mode; select Heat/Cool/Auto/Off/Em Heat; save.
4. Configure Schedule: See Settings for programming; defaults ENERGY STAR compliant.

Home Screen Navigation

1. Display: Current temp, setpoint, mode icons (heat/cool/auto/off), fan (auto/on), lock symbol, hourglass for TOV.
2. Controls: Up/Down for adjustments; Mode/Fan buttons for selection; Hold Up/Down 3s to toggle display (temp/setpoint/outdoor).
3. Indicators: Wrench for config/test; Error codes (E0-E7); solid hourglass in TOV.

Operating Modes

1. Heat: Press Mode > Up/Down to Heat; raise setpoint; flame icon.
2. Cool: Press Mode > Up/Down to Cool; lower setpoint; snowflake icon.
3. Auto: Press Mode > Up/Down to Auto; deadband enforced.
4. Off: Press Mode > Up/Down to Off; no operation.
5. Em Heat: Press Mode > Up/Down to Em Heat; aux heat bypass.
6. Fan: Press Fan > Up/Down to Auto/On.

Settings Screen

1. Configuration: Hold config button 3s; scroll options (e.g., #01 system type, #07 resolution, #12 deadband, #14 scheduling type).
2. Lock: Hold Up/Down 4s in mode to lock/unlock.
3. Schedule Editing: Enter schedule mode; select days/periods; set time/heat/cool/fan; save.
4. Test Mode: Hold config button twice; test heat/cool/fan/thermistor.
5. Reset: Cycle power; defaults via #18.

Advanced Features

1. Scheduling: 1/5+1+1/5+2/7-day; 2/4 periods (morning/day/evening/night); ENERGY STAR defaults.
2. Timed Override (TOV): Temporary changes up to 99 days/23 hrs; adjusts setpoints/fan/occupancy; hourglass indicator.
3. Cycling: Configurable CPH for efficiency.
4. Deadband: 2-9°F separation in Auto.
5. Compressor Protection: 5-10 min off time.
6. Remote Sensor: For control/lockout/display.

Troubleshooting

Installation Instructions

Warning: Qualified personnel only. Disconnect power; discharge capacitors.

Pre-Installation

Wiring Diagrams

Terminal Designations:

TerminalDescription
R24V Hot (Heating)
Rc24V Hot (Cooling)
W1Heat Relay 1
W2Heat Relay 2/Aux/Emergency
W3Heat Relay 3
GFan Relay
Y1Compressor Stage 1
Y2Compressor Stage 2
O/BReversing Valve (Heat Pump)
CCommon
S1/S2Remote Sensor

Notes: Jumper R/Rc for single transformer. Diagrams vary by system type (conventional/heat pump).

Configuration Options

  1. Mount base; connect wires per diagram.
  2. Power up; enter config mode (hold button 3s).
  3. Set #01 system type, #04/#05 CPH, #08 compressor off, #12 deadband, #14 programmable (1=enable), #23 scheduling type.
  4. Run test mode; calibrate sensors.
  5. Secure cover.

Calculation Tool

Estimate monthly energy savings from programmable scheduling (assumes 8°F setback saving 0.2 kWh per hour unoccupied; 30 days/month).