The Trane X13511537-01 (BAYSTAT150A) is a programmable 3H/2C push-button thermostat for commercial conventional and heat pump systems. It features an LCD display with symbols for temperature, setpoints, and modes, supporting Heat, Cool, Auto, Off, and Emergency Heat system modes, and On/Auto fan modes. It includes configurable scheduling (1/5+1+1/5+2/7-day), timed overrides (TOV), cycling rates, deadband, compressor protection, remote sensor compatibility, and error codes. Below are the key specifications and operation instructions.
1. Power On: Apply 24 VAC; performs power-up sequence (full screen, firmware, tests).
2. Set Time: From operating screen, press sequence to enter time mode; adjust hours/minutes with Up/Down; save.
3. Set System Mode: Press Mode; select Heat/Cool/Auto/Off/Em Heat; save.
4. Configure Schedule: See Settings for programming; defaults ENERGY STAR compliant.
1. Display: Current temp, setpoint, mode icons (heat/cool/auto/off), fan (auto/on), lock symbol, hourglass for TOV.
2. Controls: Up/Down for adjustments; Mode/Fan buttons for selection; Hold Up/Down 3s to toggle display (temp/setpoint/outdoor).
3. Indicators: Wrench for config/test; Error codes (E0-E7); solid hourglass in TOV.
1. Heat: Press Mode > Up/Down to Heat; raise setpoint; flame icon.
2. Cool: Press Mode > Up/Down to Cool; lower setpoint; snowflake icon.
3. Auto: Press Mode > Up/Down to Auto; deadband enforced.
4. Off: Press Mode > Up/Down to Off; no operation.
5. Em Heat: Press Mode > Up/Down to Em Heat; aux heat bypass.
6. Fan: Press Fan > Up/Down to Auto/On.
1. Configuration: Hold config button 3s; scroll options (e.g., #01 system type, #07 resolution, #12 deadband, #14 scheduling type).
2. Lock: Hold Up/Down 4s in mode to lock/unlock.
3. Schedule Editing: Enter schedule mode; select days/periods; set time/heat/cool/fan; save.
4. Test Mode: Hold config button twice; test heat/cool/fan/thermistor.
5. Reset: Cycle power; defaults via #18.
1. Scheduling: 1/5+1+1/5+2/7-day; 2/4 periods (morning/day/evening/night); ENERGY STAR defaults.
2. Timed Override (TOV): Temporary changes up to 99 days/23 hrs; adjusts setpoints/fan/occupancy; hourglass indicator.
3. Cycling: Configurable CPH for efficiency.
4. Deadband: 2-9°F separation in Auto.
5. Compressor Protection: 5-10 min off time.
6. Remote Sensor: For control/lockout/display.
Warning: Qualified personnel only. Disconnect power; discharge capacitors.
Terminal Designations:
| Terminal | Description |
|---|---|
| R | 24V Hot (Heating) |
| Rc | 24V Hot (Cooling) |
| W1 | Heat Relay 1 |
| W2 | Heat Relay 2/Aux/Emergency |
| W3 | Heat Relay 3 |
| G | Fan Relay |
| Y1 | Compressor Stage 1 |
| Y2 | Compressor Stage 2 |
| O/B | Reversing Valve (Heat Pump) |
| C | Common |
| S1/S2 | Remote Sensor |
Notes: Jumper R/Rc for single transformer. Diagrams vary by system type (conventional/heat pump).
Estimate monthly energy savings from programmable scheduling (assumes 8°F setback saving 0.2 kWh per hour unoccupied; 30 days/month).