The Trane X13511536-01 (BAYSTAT155A) is a non-programmable 3H/2C push-button thermostat for commercial conventional and heat pump systems. It features an LCD display with symbols for temperature, setpoints, and modes, supporting Heat, Cool, Auto, and Off system modes, and On/Auto fan modes. It includes configurable cycling rates, deadband, compressor protection, remote sensor compatibility, and error codes. Below are the key specifications and operation instructions.
1. Power On: Apply 24 VAC; performs power-up sequence (full screen, firmware, tests).
2. Configure: Remove cover, hold configuration button 3s; adjust options (#01-18) with Up/Down/Left/Right; exit after 10 min.
3. Set Modes: Press Mode/Fan; select with Up/Down.
4. Calibrate: Use remote sensor if needed; verify via test mode.
1. Display: Current temp, setpoint, mode icons (heat/cool/auto/off), fan (auto/on), lock symbol.
2. Controls: Up/Down for adjustments; Mode/Fan buttons for selection; Hold Up/Down 3s to toggle display (temp/setpoint/outdoor).
3. Indicators: Wrench for config/test; Error codes (E0-E7).
1. Heat: Press Mode > Up/Down to Heat; raise setpoint; flame icon.
2. Cool: Press Mode > Up/Down to Cool; lower setpoint; snowflake icon.
3. Auto: Press Mode > Up/Down to Auto; deadband enforced.
4. Off: Press Mode > Up/Down to Off; no operation.
5. Fan: Press Fan > Up/Down to Auto/On.
1. Configuration: Hold config button 3s; scroll options (e.g., #01 system type, #07 resolution, #12 deadband).
2. Lock: Hold Up/Down 4s in mode to lock/unlock.
3. Test Mode: Hold config button twice; test heat/cool/fan/thermistor.
4. Reset: Cycle power; defaults via #18.
1. Cycling: Configurable CPH for efficiency.
2. Deadband: 2-9°F separation in Auto.
3. Compressor Protection: 5-10 min off time.
4. Remote Sensor: For control/lockout/display.
Warning: Qualified personnel only. Disconnect power; discharge capacitors.
Terminal Designations:
| Terminal | Description |
|---|---|
| R | 24V Hot (Heating) |
| Rc | 24V Hot (Cooling) |
| W1 | Heat Relay 1 |
| W2 | Heat Relay 2/Aux/Emergency |
| G | Fan Relay |
| Y1 | Compressor Stage 1 |
| Y2 | Compressor Stage 2 |
| O/B | Reversing Valve (Heat Pump) |
| C | Common |
| S1/S2 | Remote Sensor |
Notes: Jumper R/Rc for single transformer. Diagrams vary by system type (conventional/heat pump).
Estimate monthly energy savings from adjustable cycling rates (assumes 0.1 kWh saved per cycle adjustment; 30 days/month).