Trane X13511535-01 Thermostat Operation Manual

The Trane X13511535-01 (BAYSTAT150A) is a non-programmable 1H/1C push-button thermostat for commercial conventional and heat pump systems. It features an LCD display with symbols for temperature, setpoints, and modes, supporting Heat, Cool, Auto, and Off system modes, and On/Auto fan modes. It includes configurable cycling rates, deadband, compressor protection, remote sensor compatibility, and error codes. Below are the key specifications and operation instructions.

1. Key Specifications 2. Operation Instructions 2.1. Initial Setup 2.2. Home Screen Navigation 2.3. Operating Modes 2.4. Settings Screen 2.5. Advanced Features 2.6. Troubleshooting 3. Installation Instructions 3.1. Pre-Installation 3.2. Wiring Diagrams 3.3. Configuration Options 4. Calculation Tool

Key Specifications

Operation Instructions

Initial Setup

1. Power On: Apply 24 VAC; performs power-up sequence (full screen, firmware, tests).
2. Configure: Remove cover, hold configuration button 3s; adjust options (#01-18) with Up/Down/Left/Right; exit after 10 min.
3. Set Modes: Press Mode/Fan; select with Up/Down.
4. Calibrate: Use remote sensor if needed; verify via test mode.

Home Screen Navigation

1. Display: Current temp, setpoint, mode icons (heat/cool/auto/off), fan (auto/on), lock symbol.
2. Controls: Up/Down for adjustments; Mode/Fan buttons for selection; Hold Up/Down 3s to toggle display (temp/setpoint/outdoor).
3. Indicators: Wrench for config/test; Error codes (E0-E7).

Operating Modes

1. Heat: Press Mode > Up/Down to Heat; raise setpoint; flame icon.
2. Cool: Press Mode > Up/Down to Cool; lower setpoint; snowflake icon.
3. Auto: Press Mode > Up/Down to Auto; deadband enforced.
4. Off: Press Mode > Up/Down to Off; no operation.
5. Fan: Press Fan > Up/Down to Auto/On.

Settings Screen

1. Configuration: Hold config button 3s; scroll options (e.g., #01 system type, #07 resolution, #12 deadband).
2. Lock: Hold Up/Down 4s in mode to lock/unlock.
3. Test Mode: Hold config button twice; test heat/cool/fan/thermistor.
4. Reset: Cycle power; defaults via #18.

Advanced Features

1. Cycling: Configurable CPH for efficiency.
2. Deadband: 2-9°F separation in Auto.
3. Compressor Protection: 5-10 min off time.
4. Remote Sensor: For control/lockout/display.

Troubleshooting

Installation Instructions

Warning: Qualified personnel only. Disconnect power; discharge capacitors.

Pre-Installation

Wiring Diagrams

Terminal Designations:

TerminalDescription
R24V Hot (Heating)
Rc24V Hot (Cooling)
W (O/B)Heat Relay / Changeover Valve
GFan Relay
YCompressor Stage 1
CCommon
S1/S2Remote Sensor

Notes: Jumper R/Rc for single transformer. Diagrams vary by system type (conventional/heat pump).

Configuration Options

  1. Mount base; connect wires per diagram.
  2. Power up; enter config mode (hold button 3s).
  3. Set #01 system type, #04/#05 CPH, #08 compressor off, #12 deadband.
  4. Run test mode; calibrate sensors.
  5. Secure cover.

Calculation Tool

Estimate monthly energy savings from adjustable cycling rates (assumes 0.1 kWh saved per cycle adjustment; 30 days/month).