The Trane TZEMT400 (TZEMT400AB32MAA) is a Z-Wave enabled programmable thermostat for controlling single and multistage forced air heating and cooling HVAC systems, including gas/oil/electric furnaces, heat pumps, and air conditioning. It integrates with Schlage LiNK™ and other Z-Wave systems for remote control and scheduling, features a backlit LCD display, runtime tracking, service reminders, and compatibility with 24 VAC systems. It supports 7-day scheduling (via Z-Wave or direct), emergency heat, and fan control. Below are the key specifications and operation instructions.
1. Power On: Connect 24 VAC; display activates.
2. Set Time/Date: Press MENU twice > Set Clock; adjust with Up/Down/Select; Done.
3. Z-Wave Enrollment: MENU > Installer Settings (hold middle buttons 3s) > Z-Wave > Enrollment Mode; add via controller.
4. Enable Schedules: Installer Settings > System Settings > Schedules > Enable.
1. Display: Time, room temp, setpoint, mode, fan, alerts, usage graph.
2. Controls: Up/Down for setpoint; Mode/Fan buttons; MENU for settings; Scroll/Next/Back in menus.
3. Indicators: LEDs (green off, red heat/cool, amber alerts); blinking clock on power loss.
1. Heat: Mode > Heat; raise setpoint; flame icon/LED.
2. Cool: Mode > Cool; lower setpoint; snowflake icon/LED.
3. Off: Mode > Off; no operation.
4. Auto: Mode > Auto; automatic changeover.
5. Emergency Heat: Mode > Em Heat; aux heat for heat pumps.
6. Fan: Auto (demand) or On (continuous).
1. User Menu: MENU > User Settings: Set Clock, Filter/Maint Service, Screen Timeout, F/C, Backlight/Contrast, Usage Graph, Schedules, Thermostat Info.
2. Installer Menu: Hold middle buttons 3s: System/Mechanical Settings (stages, heat pump config), Display Lock, Setpoint Limits.
3. Service Reminders: Set/reset filter (100-3650 hrs), maint (100-9999 hrs runtime).
4. Reset: Power cycle; reset clock on outage.
1. Scheduling: MENU > Schedules: Edit 7-day programs (wake/leave/return/sleep); copy days.
2. Z-Wave Remote: Setpoints/modes via app/controller; enrollment for pairing.
3. Runtime Tracking: Usage Graph for heat/cool hours; alerts for service.
4. Compressor Protection: Configurable cycle times in Installer Settings.
Warning: Professional installation. Disconnect power at breaker.
Terminal Designations (8-terminal block):
| Terminal | Description |
|---|---|
| R | 24V Hot (RC/RH, jumper JP1 if single) |
| C | 24V Common (required) |
| W1/W2 | Heat Stages/Aux |
| Y1/Y2 | Cool/Compressor Stages |
| G | Fan |
| O/B | Reversing Valve (Heat Pump) |
Notes: Diagrams for 1-2 stage heat/cool, heat pump types; cut JP1 for separate RC/RH. 18 AWG wire.
Estimate monthly energy savings from 7-day scheduling (assumes 8°F setback saving 0.2 kWh per hour unoccupied; 30 days/month).