The Trane THT02775 (BAYSTAT152A, X13511538-01) is a touch-screen programmable thermostat for conventional rooftop units, air conditioners, and heat pumps. It features an LCD touch screen, support for 1-3 stage heat/1-2 stage cool, scheduling (2/4 periods, up to 7-day), temporary overrides, dehumidification, economizer/TOD control, remote sensors, and lockout features. Below are the key specifications and operation instructions.
1. Power On: Apply 24 Vac; performs self-test, displays errors if any (e.g., E1 low voltage).
2. Set Time/Date: Touch clock icon; adjust hours/minutes/day/month/year; save.
3. Set Mode/Fan: Select system (off/heat/cool/auto) and fan (auto/on) from home screen.
4. Installer Config: Access menu for initial options (e.g., temp units, system type).
1. Display: Current temp, setpoints, time/day, mode icons, occupancy, filter/error alerts.
2. Controls: Touch arrows for setpoints; mode/fan boxes for selection; menu for settings.
3. Indicators: Flame/snowflake for active modes; blinking filter/error; hourglass for TOV.
1. Heat: Select Heat; raise setpoint; activates stages with flame icon.
2. Cool: Select Cool; lower setpoint; activates stages with snowflake icon.
3. Auto: Automatic changeover (manual/auto via config).
4. Off: No operation.
5. Em Heat: For heat pumps; aux heat bypass.
6. Fan: Auto (with system) or On (continuous).
1. Access Menu: Touch menu; select time/schedule/dehumidify.
2. Schedule: Set periods (2/4), day groups; adjust time/heat/cool/fan/occupancy per period.
3. Filter Reset: Hold arrows 3s.
4. Offsets: Adjust temp/humidity (±6°F/°C).
5. Lockout: Requires code (default 0000) for changes.
1. TOV: Touch fan box; quick (up to 4 hrs) or configurable (0.5-8 hrs); shows remaining time.
2. Dehumidification: Enable via config; controls with remote sensor.
3. CPH/Lockouts: Cycles per hour (1-10); temp-based compressor/aux lockout (40-70°F).
4. Display Options: Local/remote/outdoor temp/humidity; fan-on extension (40s heat/90s cool).
Warning: Qualified personnel only. Disconnect power. Follow lockout/tagout.
Terminal Designations:
| Terminal | Description |
|---|---|
| R | 24V Hot (Heating) |
| Rc | 24V Hot (Cooling) |
| W1/W2 | Heat Stages/Aux |
| Y1/Y2 | Compressor Stages |
| G | Fan |
| O/B | Reversing Valve |
| E | Emergency Heat |
| DH | Dehumidify |
| S1/S2 | Remote Temp Sensor |
| Hp/Hs | Humidity Sensor |
| C | Common |
Notes: Jumper R-Rc for single transformer. Diagrams for 1-3H/1-2C conventional/heat pump; remote sensors (10kΩ NTC temp, 4-20mA humidity).
Estimate monthly energy savings from 4-period scheduling (assumes 8°F setback saving 0.2 kWh per hour unoccupied; 30 days/month).