Trane THT02775 Thermostat Operation Manual

The Trane THT02775 (BAYSTAT152A, X13511538-01) is a touch-screen programmable thermostat for conventional rooftop units, air conditioners, and heat pumps. It features an LCD touch screen, support for 1-3 stage heat/1-2 stage cool, scheduling (2/4 periods, up to 7-day), temporary overrides, dehumidification, economizer/TOD control, remote sensors, and lockout features. Below are the key specifications and operation instructions.

1. Key Specifications 2. Operation Instructions 2.1. Initial Setup 2.2. Home Screen Navigation 2.3. Operating Modes 2.4. Settings Screen 2.5. Advanced Features 2.6. Troubleshooting 3. Installation Instructions 3.1. Pre-Installation 3.2. Wiring Diagrams 3.3. Configuration Options 4. Calculation Tool

Key Specifications

Operation Instructions

Initial Setup

1. Power On: Apply 24 Vac; performs self-test, displays errors if any (e.g., E1 low voltage).
2. Set Time/Date: Touch clock icon; adjust hours/minutes/day/month/year; save.
3. Set Mode/Fan: Select system (off/heat/cool/auto) and fan (auto/on) from home screen.
4. Installer Config: Access menu for initial options (e.g., temp units, system type).

Home Screen Navigation

1. Display: Current temp, setpoints, time/day, mode icons, occupancy, filter/error alerts.
2. Controls: Touch arrows for setpoints; mode/fan boxes for selection; menu for settings.
3. Indicators: Flame/snowflake for active modes; blinking filter/error; hourglass for TOV.

Operating Modes

1. Heat: Select Heat; raise setpoint; activates stages with flame icon.
2. Cool: Select Cool; lower setpoint; activates stages with snowflake icon.
3. Auto: Automatic changeover (manual/auto via config).
4. Off: No operation.
5. Em Heat: For heat pumps; aux heat bypass.
6. Fan: Auto (with system) or On (continuous).

Settings Screen

1. Access Menu: Touch menu; select time/schedule/dehumidify.
2. Schedule: Set periods (2/4), day groups; adjust time/heat/cool/fan/occupancy per period.
3. Filter Reset: Hold arrows 3s.
4. Offsets: Adjust temp/humidity (±6°F/°C).
5. Lockout: Requires code (default 0000) for changes.

Advanced Features

1. TOV: Touch fan box; quick (up to 4 hrs) or configurable (0.5-8 hrs); shows remaining time.
2. Dehumidification: Enable via config; controls with remote sensor.
3. CPH/Lockouts: Cycles per hour (1-10); temp-based compressor/aux lockout (40-70°F).
4. Display Options: Local/remote/outdoor temp/humidity; fan-on extension (40s heat/90s cool).

Troubleshooting

Installation Instructions

Warning: Qualified personnel only. Disconnect power. Follow lockout/tagout.

Pre-Installation

Wiring Diagrams

Terminal Designations:

TerminalDescription
R24V Hot (Heating)
Rc24V Hot (Cooling)
W1/W2Heat Stages/Aux
Y1/Y2Compressor Stages
GFan
O/BReversing Valve
EEmergency Heat
DHDehumidify
S1/S2Remote Temp Sensor
Hp/HsHumidity Sensor
CCommon

Notes: Jumper R-Rc for single transformer. Diagrams for 1-3H/1-2C conventional/heat pump; remote sensors (10kΩ NTC temp, 4-20mA humidity).

Configuration Options

  1. Mount backplate; connect wires per system diagram.
  2. Power up; access installer menu (hold screen or code).
  3. Set options: System type (0130), scheduling (0140/0230), CPH (0160), lockouts (0180), dehum (0170).
  4. Run tests (1-15) for outputs/stages.
  5. Program schedule; factory reset if needed (0300).

Calculation Tool