The Trane TCONT602AF22MA is a programmable comfort control thermostat for 24 VAC single- and multi-stage heating and cooling systems, including gas, oil, electric heat, and heat pumps. It supports manual or auto changeover and requires a common wire for power. Features include a large backlit LCD display, keypad controls for modes, fan, and energy savings, with filter reminders and outdoor temperature calibration. Below are the key specifications and operation instructions.
1. Power On: Connect to system; display shows room temp.
2. User Setup: Hold MODE + FAN; navigate with MODE (forward)/FAN (back); set filter timer, clock, deadband.
3. Calibrate Outdoor: Adjust +5 to -5°F.
4. Set Mode: MODE for Heat/Em Heat/Cool/Auto/Off.
5. Set Fan: FAN for Auto/Continuous.
1. Display: Current mode with border; "FAN ON" for continuous; "FILTER/OD" flashing; energized equipment indicator.
2. Controls: MODE for modes; FAN for fan; FILTER/OD for outdoor/reminder; Energy Savings for adjustments.
3. Outdoor Temp: Press FILTER/OD to view.
4. Filter Reminder: Press FILTER/OD twice for days remaining.
1. Energy Savings: Press Energy Savings; shifts setpoints for efficiency.
2. Filter Reminder: Preset days; reset via FILTER/OD.
3. Auto Changeover: In Auto, presets switch per deadband.
1. Access: Hold MODE + FAN for User Setup; MODE/FAN to navigate.
2. Options: Filter timer (days/reset); Outdoor calibration (±5°F); Deadband (degrees); Clock.
3. Changes: Immediate; Done to save.
1. Emergency Heat: MODE to Em Heat; bypasses compressor.
2. Fan Continuous: FAN to Continuous; "FAN ON" displays.
3. Energy Savings: Adjusts setpoints for reduced use.
4. Auto Changeover: MODE to Auto; switches per deadband.
Warning: Professional only. Disconnect power.
1H/1C (1 transformer):
| Terminal | Connection |
|---|---|
| R | Power |
| W | Heat |
| Y | Cool |
| G | Fan |
| B | Common |
2H/2C (1 transformer):
| Terminal | Connection |
|---|---|
| R | Power |
| W1 | Heat 1 |
| W2 | Heat 2 |
| Y1 | Cool 1 |
| Y2 | Cool 2 |
| G | Fan |
| B | Common |
Notes: Remove jumper for 2 transformers; connect B for common.
Estimate monthly energy savings from energy savings mode (assumes 2°F shift, 0.5 kWh/hr saved; 30 days/month).