The Trane TCONT103 (XR103) is a non-programmable 2H/1C digital thermostat for heat pump systems. It features a 2-inch digital display, support for 2-stage heat/1-stage cool, and compatibility with Trane systems like TAM Series, S9V2 Furnace, Variable Speed Gas Furnace, and GAT2/GAM2/TEM3/TEM4. It supports malfunction indicators, reversing valve control (O/B), and aux heat during defrost. Below are the key specifications and operation instructions.
1. Install per Wiring: Follow installation instructions for mounting and wiring.
2. Power On: Connect to 24V system; display activates.
3. Set System Mode: SYSTEM switch to Heat/Cool/Off/Auto.
4. Adjust Temperature: Use UP/DOWN arrows for setpoint.
1. Display: Shows room temperature, setpoint, mode icons (flame for heat, snowflake for cool), malfunction indicator.
2. Controls: SYSTEM switch for modes; FAN for Auto/On; UP/DOWN for adjustments.
3. Indicators: Malfunction light, mode icons.
1. Heat: SYSTEM to Heat; raise setpoint with UP; flame icon; blower on high speed then warm air.
2. Cool: SYSTEM to Cool; lower setpoint with DOWN; snowflake icon; blower on high speed then cold air.
3. Off: SYSTEM to Off; no operation.
4. Auto: SYSTEM to Auto for automatic changeover.
5. Fan: Auto (with system) or On (continuous).
1. Temperature Adjustment: Use UP/DOWN buttons directly on home screen.
2. Mode Selection: Via SYSTEM switch.
3. Reset: See Troubleshooting for reset procedure.
4. No advanced settings like °F/°C or backlight specified.
1. Aux Heat: Energizes via X2 during defrost cycle.
2. Malfunction Indicator: Displays if system issue detected.
3. Reversing Valve: Controlled via O/B terminal based on system configuration.
Warning: Professional installation. Disconnect power. Comply with all codes.
Terminal Designations (based on configurations):
| Terminal | Description |
|---|---|
| R/RH | 24V Power |
| RC | 24V Power (Cooling, if separate) |
| W1/W2 | Heating Stages (Aux Heat) |
| G | Fan Relay |
| Y/Y1 | Cooling/Compressor Relay |
| O/B | Reversing Valve (Heat Pump) |
| X2 | Aux Heat during Defrost |
Notes: Connect condensate switches between Y and Y1. Use X2 for aux heat in defrost. Select diagram based on system (e.g., TAM Series, Variable Speed Gas Furnace). Remove jumpers if 2-transformer system.