The Trane SENS-IN-1D18-HD60D29-4 is a programmable zone sensor designed for constant volume (CV) units and heat pump (HP) units in packaged systems. It enables 7-day programming with 2, 3, or 4 periods per day for occupied/unoccupied modes, supporting features like morning warm-up, pre-cool, and temporary overrides. Compatible with Trane packaged rooftop and self-contained units, it communicates via the Network Sensor Bus (NSB) for efficient zone control. Below are the key specifications and operation instructions.
1. Power On: Apply power; verify wiring before startup.
2. Set Time: Press "+" or "-" side of TIME key to adjust in one-minute intervals; day auto-advances.
3. Programming Menu: Select mode (Occupied/Unoccupied) with MODE key; set periods, setpoints, and options.
4. Option Menu: Configure morning warm-up, pre-cool, economy mode.
1. Normal Run State: Displays time, zone temperature, heat/cool setpoints, day, status icons (HEAT, COOL, SYSTEM ON, SERVICE).
2. Controls: MODE key for system mode; FAN key for ON/AUTO; UP/DOWN arrows for temporary adjustments.
3. Indicators: Flashing colon for system ON; override screen for temporary changes.
1. Access Programming Menu: Select Occupied/Unoccupied with MODE key; program up to 4 periods (Morn, Day, Eve, Nite) with start times, heat/cool setpoints, status.
2. Preset Periods: Weekly schedule for each day; ERASE key to clear entries.
3. Morning Warm-Up: Automatically heats if 2°F below setpoint during unoccupied-to-occupied transition (Option 0: Disabled/1: Enabled).
4. Morning Pre-Cool: Similar for cooling (Option 1: Disabled/1: Enabled).
1. Option Menu: Access to set morning warm-up (0/1), pre-cool (0/1), economy mode (0/1).
2. Temporary Override: Change temperature, mode, zone status (Occupied/Unoccupied), fan (ON/AUTO) for a period.
3. Zone Status Toggle: Hold UP and DOWN for 2 seconds.
4. Exit: Press MODE or timeout.
1. UCM Status Inputs: Receives signals (HEAT, COOL, SYSTEM ON, SERVICE) via terminals 7-10; SERVICE icon for alerts (ON: service needed; flashing: fan failure).
2. Economy Mode: Reduces energy use (Option 2: Disabled/1: Enabled).
3. Test Mode: Flashing TEST icon during testing.
4. Supply Air Sensor: Optional monitoring.
Warning: Experienced HVAC technicians only. Disconnect power before wiring. Comply with national/state/local codes.
Connect to UCM and power:
| Terminal | Connection |
|---|---|
| 7 | HEAT (to UCM) |
| 8 | COOL (to UCM) |
| 9 | SYSTEM ON (to UCM) |
| 10 | SERVICE (to UCM) |
| 11/14 | 24 VAC Power |
| 11/12 | Communications (22-42 VDC) |
Note: Optional UCM status inputs (4 wires); mount sub-base with screws, hook sensor tabs.
Estimate monthly energy savings from scheduling setback (assumes 0.3 kWh per °F per hour; 2°F morning warm-up threshold factored).