The Trane RT-SVU010A-GB is a versatile thermostat available in programmable and non-programmable models for controlling residential heating and cooling systems, including conventional and heat pump configurations. It features an LCD display for temperature, setpoints, and modes, with programmable options supporting up to four periods per day for energy-efficient scheduling. Compatible with single- and multi-stage systems, it includes automatic changeover, fan control, and optional remote sensors. Below are the key specifications and operation instructions.
1. Power On: Apply power; thermostat runs power-up test (displays firmware version).
2. Set Time/Date: For programmable: Hold arrows + Mode + Fan + Prog for 3s; adjust hour/minute.
3. System Mode: Press Mode to cycle Off/Heat/Cool/Auto/Em Heat.
4. Fan Mode: Press Fan for Auto/On.
1. Display: Current temp, setpoint, mode, fan, time/day (programmable), period.
2. Toggle Views: Hold arrows for 3s to cycle temp/setpoint/outdoor (if sensor).
3. Adjust: Arrows for setpoints; Mode/Fan buttons to change.
(Programmable Only)
1. Enable: Press Prog; select days/periods.
2. Periods: 2 or 4 per day (e.g., morning 70°F heat/78°F cool; defaults vary).
3. TOV Override: Adjust arrows, then set duration (up to 4 hrs), fan, occupancy.
4. Non-Programmable: Manual setpoints only.
1. Access: Hold config button 3s; scroll with arrows.
2. Key Settings: Temp resolution, clock format, deadband (2-9°F), CPH rates, lockouts.
3. Lock: Hold arrows 4s (icon shows).
4. Exit: Press config or wait 10 min.
1. Remote Sensor: Config to display/use outdoor temp for lockouts (e.g., compressor below 45°F).
2. Aux Heat: Comfort/economy mode (non-programmable).
3. Economizer: A terminal for TOD/cool calls.
4. Extended Fan: 90s post-heat, 40s post-cool.
5. Emergency Heat: Manual activation; L terminal indicator.
Warning: Only qualified personnel should install. Disconnect power before wiring. Max wire resistance 2.5 ohms.
For 3H/2C Heat Pump with Aux (jumper Rc/R if single transformer):
| Terminal | Connection |
|---|---|
| Rc/R | 24V Power |
| Y/Y2 | Compressor Stages 1/2 |
| O/B | Changeover Valve (O in Cool) |
| W/Aux | Aux Heat |
| W2/E | Emergency/Aux Heat |
| G | Fan |
| C | Common |
| L | Emergency Indicator |
| A | Economizer/TOD |
| S1/S2 | Remote Sensor |
Note: Programmable has two terminal blocks; see manual figures for dual transformer.
Estimate stage 1 runtime percentage based on temperature difference (ΔT) and cycles per hour (CPH). Assumes duty cycle = ΔT / 20 (capped at 100%); runtime % = duty cycle * 100.