The Trane Pivot BAYSTAT814 Series is a programmable smart thermostat with a color touch-screen and intuitive user interface for easy operation. It features built-in remote access capability, allowing users to control it via mobile devices (iOS or Android). The thermostat supports configurations for heat/cool, dual fuel, heat only, cooling only, and heat pump systems. It uses proprietary PI control schemes for comfort and energy efficiency. Below are the key specifications and operation instructions.
1. Power-Up: Sequence lasts 90–120 seconds; screen calibration available for 5 seconds (or 5 minutes post-reset).
2. Connect Network: Wi-Fi (within 30 ft of router) or Ethernet; register for remote access via app.
3. Installer Setup: Home > Menu > Service > Technician Access (5s) > Proceed > Service Menu; configure system type, sensors, accessories.
4. Demand Response: Home > Menu > System Info > Demand Response registration.
1. Display: Indoor temperature, RH, setpoints, system status, widgets (e.g., occupancy).
2. Touch Controls: Mode, fan, schedule; energized terminals in green on system report.
3. Menu: Access settings, service, diagnostics.
1. Scheduling: Occupied/unoccupied modes; fan continuous in occupied On, auto in unoccupied.
2. Periods: Up to multiple periods/day with recovery to reach setpoints by start.
3. Presets: Heating/cooling setpoints, RH targets; optimal recovery based on outdoor temp.
1. Installer Setup Groups: Group 1: Equipment type, changeover (auto/manual, 2°F deadband).
2. Group 2: Staging (1–2 stages, airflow %).
3. Group 3: Sensors (Internet weather/ODT, remote, binary inputs).
4. Group 4: Accessories (filtration, humidifier on Aux1/Aux2, dehumidifier).
5. Group 5: Comfort (RH targets, continuous fan).
6. Group 6: Staging details (airflow %).
7. Group 7: Lockouts (aux/compressor OAT-based).
8. Reminders: Filters, UV, etc.
1. Humidifier: RH control below heating target; frost control offsets based on OAT.
2. Optimal Start/Stop: Calculates start using outdoor temp; stop preempts unoccupied.
3. Dehumidification: During cooling; reduces airflow 30% if RH > target (Trane variable speed).
4. Dual Fuel: Locks compressor below OAT, switches to aux; balance point.
5. OADR: Demand response for peak days.
Warning: Qualified personnel only; hazards in HVAC equipment risk death/injury. Follow precautions; non-Trane personnel comply with local regs. Separate sensor wires from high-voltage.
For Trane Reliatel 1/2-stage constant volume (non-variable blower):
| Terminal | Connection |
|---|---|
| R | 24V Power |
| C | Common |
| G | Fan |
| Y1/Y2 | Cool Stages |
| W1/W2 | Heat Stages |
| O/B | Changeover (HP) |
| AUX1/AUX2 | Accessories (Humidifier/Dehum) |
| ODT | Outdoor Temp Sensor |
| RS1 | Binary Input (Occupancy) |
Note: Up to 2 stages; for economizer, Aux1 as ventilation (60 min/hour); full diagrams in manual.
Estimate monthly energy savings from optimal start/stop and duty cycles (assumes 0.3 kWh per °F per hour; 30 days/month).