Trane BAYSENS924 Thermostat Operation Manual

The Trane BAYSENS924 is a commercial touch screen programmable zone sensor designed for ReliaTel™ controlled systems like Precedent™, Voyager™, and Odyssey™ units. It features an intuitive color LCD interface, 7-day scheduling with up to three occupied/unoccupied events, demand shed functionality, and BACnet MS/TP communication. Compatible with UC400, Symbio™ 700/800 controllers for WSHP, fan coils, and unit ventilators. Below are the key specifications and operation instructions.

1. Key Specifications 2. Operation Instructions 2.1. Initial Setup 2.2. Home Screen Navigation 2.3. Scheduling and Presets 2.4. Settings Screen 2.5. Advanced Features 2.6. Troubleshooting 3. Installation Instructions 3.1. Pre-Installation 3.2. Wiring Diagrams 3.3. Configuration Options 4. Calculation Tool

Key Specifications

Operation Instructions

Initial Setup

1. Power On: Snap cover on base; displays "Power on" then Home Screen; adjust clock if prompted.
2. Prerequisites: Ensure ReliaTel™/Symbio™ in correct mode (e.g., EFlex "DISPLAY READ ONLY"); provide operational schedule.
3. Installer Access: Enter password 4017 via Setup menu for configuration.

Home Screen Navigation

1. Display: Shows occupancy, temp, mode (off/auto/cool/heat), fan (auto/on), time; tap icons for controls.
2. Adjustments: Use up/down arrows for setpoints (1° increments); tap for mode/fan toggle.
3. Standby: Activates after inactivity; tap to wake.

Scheduling and Presets

1. Access: Tap Schedule icon; set clock/date, up to 3 occ/unocc events/day.
2. Types: 7-day, 5+2, 5+1+1; enable/disable via config.
3. Overrides: Tap corner for temp/occ toggle (15-240 min duration); crew limited to ±2-3°F for 1-2 hrs.

Settings Screen

1. Access: Setup menu (password 4017); navigate Configuration, Setpoints, Display, Network.
2. Key Settings: Setpoints (occ/unocc cool/heat), deadband (2-10°F), backlight (0-100%), language/units.
3. Security: User/main passwords; lock setpoints/schedules.

Advanced Features

1. Demand Shed: Dry contact input offsets setpoints (4-5°F); optional system off.
2. Economizer: Enable with temp/enthalpy setpoints; optimal start/stop.
3. Standby Mode: Motion-activated offset (2-5°F) during occ.
4. Service View: Monitors firmware, temps, faults, RH, equipment status.

Troubleshooting

Installation Instructions

Warning: Qualified personnel only. Disconnect power; follow lockout/tagout. Plenum-rated; avoid direct sun/heat/drafts.

Pre-Installation

Wiring Diagrams

For ReliaTel™: Power to RTRM, comm to BCI-R (set dials 0-0-1, BACnet link).

TerminalConnection
524 Vac Power
6Power Common
13BACnet +
14BACnet -
15BACnet REF (Shield)
16/18Demand Shed (Dry Contact)
17/18Motion/Occ or Temp Sensor

Note: Polarity sensitive; ground shield at RTRM J7-COM.

Configuration Options

  1. Enter Setup (password 4017); set schedule access, calibration, economizer.
  2. Setpoints: Occ/unocc cool/heat, deadband, max/min limits.
  3. Display: Theme, language, backlight, RH enable.
  4. Network: Addresses (0-127), baud; reset instance with R button.

Calculation Tool

Estimate monthly energy savings from unoccupied setback (assumes 0.3 kWh per °F per hour; based on 3% energy per °F, 30 days/month).