The Trane BAYSENS924 is a commercial touch screen programmable zone sensor designed for ReliaTel™ controlled systems like Precedent™, Voyager™, and Odyssey™ units. It features an intuitive color LCD interface, 7-day scheduling with up to three occupied/unoccupied events, demand shed functionality, and BACnet MS/TP communication. Compatible with UC400, Symbio™ 700/800 controllers for WSHP, fan coils, and unit ventilators. Below are the key specifications and operation instructions.
1. Power On: Snap cover on base; displays "Power on" then Home Screen; adjust clock if prompted.
2. Prerequisites: Ensure ReliaTel™/Symbio™ in correct mode (e.g., EFlex "DISPLAY READ ONLY"); provide operational schedule.
3. Installer Access: Enter password 4017 via Setup menu for configuration.
1. Display: Shows occupancy, temp, mode (off/auto/cool/heat), fan (auto/on), time; tap icons for controls.
2. Adjustments: Use up/down arrows for setpoints (1° increments); tap for mode/fan toggle.
3. Standby: Activates after inactivity; tap to wake.
1. Access: Tap Schedule icon; set clock/date, up to 3 occ/unocc events/day.
2. Types: 7-day, 5+2, 5+1+1; enable/disable via config.
3. Overrides: Tap corner for temp/occ toggle (15-240 min duration); crew limited to ±2-3°F for 1-2 hrs.
1. Access: Setup menu (password 4017); navigate Configuration, Setpoints, Display, Network.
2. Key Settings: Setpoints (occ/unocc cool/heat), deadband (2-10°F), backlight (0-100%), language/units.
3. Security: User/main passwords; lock setpoints/schedules.
1. Demand Shed: Dry contact input offsets setpoints (4-5°F); optional system off.
2. Economizer: Enable with temp/enthalpy setpoints; optimal start/stop.
3. Standby Mode: Motion-activated offset (2-5°F) during occ.
4. Service View: Monitors firmware, temps, faults, RH, equipment status.
Warning: Qualified personnel only. Disconnect power; follow lockout/tagout. Plenum-rated; avoid direct sun/heat/drafts.
For ReliaTel™: Power to RTRM, comm to BCI-R (set dials 0-0-1, BACnet link).
| Terminal | Connection |
|---|---|
| 5 | 24 Vac Power |
| 6 | Power Common |
| 13 | BACnet + |
| 14 | BACnet - |
| 15 | BACnet REF (Shield) |
| 16/18 | Demand Shed (Dry Contact) |
| 17/18 | Motion/Occ or Temp Sensor |
Note: Polarity sensitive; ground shield at RTRM J7-COM.
Estimate monthly energy savings from unoccupied setback (assumes 0.3 kWh per °F per hour; based on 3% energy per °F, 30 days/month).