The Trane BAYSENS019C is a programmable zone sensor designed for use with Constant Volume (CV) units and Heat Pump (HP) units, including 3-25 Ton Packaged Heat/Cool Units (ASYSTAT666C), 3-20 Ton Packaged Heat Pump Units, and 27.5-50 Ton Packaged Rooftop Units. It features 7-day scheduling with four periods per day, temporary overrides, morning warm-up, and communication via the Network Sensor Bus (NSB) with the Unit Control Module (UCM). Below are the key specifications and operation instructions.
1. Power On: After installation, apply power; displays Normal Run State with time, temperature, and mode.
2. Defaults: Clock at 12:00 AM Monday; unoccupied heat/cool setpoints.
3. Configure: Press PROGRAM + MODE for 4 sec to enter Option Menu for initial settings like morning warm-up.
1. Normal Run State: Shows time, zone temperature, heat/cool setpoints, day, and status icons (HEAT, COOL, FAN).
2. Controls: Use UP/DOWN arrows to navigate, TIME +/- for adjustments, DAY for toggling.
3. Indicators: Flashing colon for system ON; override screen for temporary changes.
1. Access Programming Menu: Hold PROGRAM for 2 sec; set 7-day schedule with 4 periods (start time, occupied/unoccupied, setpoints, supply air).
2. Preset Periods: Occupied/Unoccupied modes with heat/cool setpoints; supports warmup during transitions.
3. Exit: Hold PROGRAM for 2 sec to save.
1. Option Menu: Press PROGRAM + MODE for 4 sec; use arrows to select options (e.g., morning warm-up: 0=disabled/1=enabled).
2. Temporary Override: Press HOLD TEMP; set new temperature, duration (hours/days via TIME +/- and DAY toggle).
3. Clock Format: 12/24 hour; exit by pressing PROGRAM for 2 sec.
1. Morning Warm-Up: Automatically heats if zone is 2°F below setpoint during unoccupied-to-occupied transition.
2. Supply Air Sensor: Enable/disable via options for monitoring.
3. Test Mode: Flashing TEST icon; SERVICE icon for alerts via terminal 10.
4. Economizer/Changeover: Optional enable for advanced control.
Warning: Experienced HVAC technicians only. CAUTION: Potentially hazardous; may cause minor/moderate injury. Disconnect power before wiring.
Connect to UCM and power source:
| Terminal | Connection |
|---|---|
| 7 | HEAT (to UCM) |
| 8 | COOL (to UCM) |
| 9 | SYSTEM ON (to UCM) |
| 10 | SERVICE (to UCM) |
| 11/14 | 24 VAC Power |
| 11/12 | Communications (22-32 VDC) |
| Distance | Wire Size |
|---|---|
| Up to 150 ft | 22 AWG |
| 151-250 ft | 20 AWG |
| 251-400 ft | 18 AWG |
| 401-600 ft | 16 AWG |
Note: Use convention for UCM connections; optional auxiliary relay wiring.
| Option | Value | Default | Description |
|---|---|---|---|
| Morning warm-up | 0=Disabled, 1=Enabled | 0 | Heat if 2°F below during transition |
| Supply air temp sensor | 0=Disabled, 1=Enabled | 0 | Enables monitoring |
| Economizer | 0=Disabled, 1=Enabled | 0 | Enables economizer |
| Changeover | 0=Disabled, 1=Enabled | 0 | Enables changeover |
Estimate monthly energy savings from morning warm-up vs. no scheduling (assumes 0.4 kWh per °F per hour; 2°F threshold factored; 20 days/month).