Trane BAYSENS019C Thermostat Operation Manual

The Trane BAYSENS019C is a programmable zone sensor designed for use with Constant Volume (CV) units and Heat Pump (HP) units, including 3-25 Ton Packaged Heat/Cool Units (ASYSTAT666C), 3-20 Ton Packaged Heat Pump Units, and 27.5-50 Ton Packaged Rooftop Units. It features 7-day scheduling with four periods per day, temporary overrides, morning warm-up, and communication via the Network Sensor Bus (NSB) with the Unit Control Module (UCM). Below are the key specifications and operation instructions.

1. Key Specifications 2. Operation Instructions 2.1. Initial Setup 2.2. Home Screen Navigation 2.3. Scheduling and Presets 2.4. Settings Screen 2.5. Advanced Features 2.6. Troubleshooting 3. Installation Instructions 3.1. Pre-Installation 3.2. Wiring Diagrams 3.3. Configuration Options 4. Calculation Tool

Key Specifications

Operation Instructions

Initial Setup

1. Power On: After installation, apply power; displays Normal Run State with time, temperature, and mode.
2. Defaults: Clock at 12:00 AM Monday; unoccupied heat/cool setpoints.
3. Configure: Press PROGRAM + MODE for 4 sec to enter Option Menu for initial settings like morning warm-up.

Home Screen Navigation

1. Normal Run State: Shows time, zone temperature, heat/cool setpoints, day, and status icons (HEAT, COOL, FAN).
2. Controls: Use UP/DOWN arrows to navigate, TIME +/- for adjustments, DAY for toggling.
3. Indicators: Flashing colon for system ON; override screen for temporary changes.

Scheduling and Presets

1. Access Programming Menu: Hold PROGRAM for 2 sec; set 7-day schedule with 4 periods (start time, occupied/unoccupied, setpoints, supply air).
2. Preset Periods: Occupied/Unoccupied modes with heat/cool setpoints; supports warmup during transitions.
3. Exit: Hold PROGRAM for 2 sec to save.

Settings Screen

1. Option Menu: Press PROGRAM + MODE for 4 sec; use arrows to select options (e.g., morning warm-up: 0=disabled/1=enabled).
2. Temporary Override: Press HOLD TEMP; set new temperature, duration (hours/days via TIME +/- and DAY toggle).
3. Clock Format: 12/24 hour; exit by pressing PROGRAM for 2 sec.

Advanced Features

1. Morning Warm-Up: Automatically heats if zone is 2°F below setpoint during unoccupied-to-occupied transition.
2. Supply Air Sensor: Enable/disable via options for monitoring.
3. Test Mode: Flashing TEST icon; SERVICE icon for alerts via terminal 10.
4. Economizer/Changeover: Optional enable for advanced control.

Troubleshooting

Installation Instructions

Warning: Experienced HVAC technicians only. CAUTION: Potentially hazardous; may cause minor/moderate injury. Disconnect power before wiring.

Pre-Installation

Wiring Diagrams

Connect to UCM and power source:

TerminalConnection
7HEAT (to UCM)
8COOL (to UCM)
9SYSTEM ON (to UCM)
10SERVICE (to UCM)
11/1424 VAC Power
11/12Communications (22-32 VDC)
DistanceWire Size
Up to 150 ft22 AWG
151-250 ft20 AWG
251-400 ft18 AWG
401-600 ft16 AWG

Note: Use convention for UCM connections; optional auxiliary relay wiring.

Configuration Options

  1. Mount sub base with screws (on wall or 2x4 box); hook ZSM top tabs and lock.
  2. Power up for initial screen.
  3. Enter Option Menu: Set morning warm-up, supply air sensor, economizer, changeover per table.
  4. Program schedule via Programming Menu.
OptionValueDefaultDescription
Morning warm-up0=Disabled, 1=Enabled0Heat if 2°F below during transition
Supply air temp sensor0=Disabled, 1=Enabled0Enables monitoring
Economizer0=Disabled, 1=Enabled0Enables economizer
Changeover0=Disabled, 1=Enabled0Enables changeover

Calculation Tool

Estimate monthly energy savings from morning warm-up vs. no scheduling (assumes 0.4 kWh per °F per hour; 2°F threshold factored; 20 days/month).