The Trane ASYSTAT666C is a programmable zone sensor thermostat designed for use with Trane constant volume (CV) and heat pump (HP) units, including 3-25 ton packaged heat/cool systems and 3-20 ton packaged heat pump units. It features a 7-day programmable schedule with four periods per day, temporary overrides, morning warm-up functionality, and communication with the Unit Control Module (UCM) via the Network Sensor Bus (NSB). Ideal for zoned HVAC control in commercial/residential applications, it provides efficient temperature management and status indicators. Below are the key specifications and operation instructions.
1. Power On: After installation, displays Normal Run State Screen showing zone temperature and setpoints.
2. Enter Option Menu: Press PROGRAM and MODE keys simultaneously for 4 seconds to configure initial settings.
3. Verify: Check clock, enable morning warm-up (default: enabled).
1. Normal Run State: Displays zone temperature, heat/cool setpoints, time, day, and status icons.
2. Controls: Use UP/DOWN arrows to navigate, TIME +/- for adjustments, DAY for toggling.
3. Indicators: Flashing colon for system ON; override screen for temporary changes.
1. Access Programming Menu: Press PROGRAM; set 7-day schedule with 4 periods (start time, occupied/unoccupied, setpoints, supply air).
2. Preset Periods: Occupied/Unoccupied modes with heat/cool setpoints; supports warmup during transitions.
3. Exit: Hold PROGRAM for 2 seconds.
1. Option Menu: Press PROGRAM + MODE for 4 sec; use arrows to select options (e.g., morning warm-up: 0=disabled/1=enabled).
2. Temporary Override: Press HOLD TEMP; set new temperature, duration (hours/days via TIME +/- and DAY toggle).
3. Clock Format: 12/24 hour; exit by pressing PROGRAM for 2 sec.
1. Morning Warm-Up: Automatically heats if zone is 2°F below setpoint during unoccupied-to-occupied transition.
2. Supply Air Sensor: Enable/disable via options for monitoring.
3. Test Mode: Flashing TEST icon; SERVICE icon for alerts via terminal 10.
4. Auxiliary Relay: Optional for additional control.
Warning: Installation by experienced HVAC technicians only. Disconnect power before wiring. Follow safety cautions to avoid equipment damage.
Connect to UCM and power source:
| Terminal | Connection |
|---|---|
| 7 | HEAT (to UCM) |
| 8 | COOL (to UCM) |
| 9 | SYSTEM ON (to UCM) |
| 10 | SERVICE (to UCM) |
| 11/14 | 24 VAC Power |
| 11/12 | Communications (22-32 VDC) |
Note: Use convention for UCM connections; optional auxiliary relay wiring.